PRECIZ · NEUTRON OPC UA

Neutron OPC UA — integration manual

OPC UA integration for Neutron: secure connections, live weighing data, stable capture and PLC/SCADA integration.

1. Overview and supported features

Neutron OPC UA

Manual revision: 1.0 · Date: 17 October 2026
Applies to: Neutron firmware 2.5.0 with OPC UA support · Vendor information model 1.2.0

Neutron by PRECIZ provides an OPC UA server for integration with PLCs, SCADA, MES and PC applications. The interface uses OPC UA Client/Server communication over UA-TCP with UA Binary encoding.

The server provides:

  • Live gross, net, tare and high-resolution gross weight, raw ADC, stability, scale status, error code and unit.

  • Measurement metadata: division, decimal places, capacity, engineering units and engineering range.

  • Device identification and standard OPC UA server information.

  • Data-change subscriptions for live values.

  • A coherent measurement read containing eleven fields from one snapshot.

  • Asynchronous capture and retrieval of a fresh stable measurement.

  • Tare, preset tare, zero and clear tare operations.

  • Filter setting FT and ADC chopping setting FC.

  • Two simultaneous client sessions.

  • Optional encrypted communication, application certificate trust and user permissions for reading or reading and executing commands.

All exposed process variables are read-only. Operations are performed through methods. The interface does not provide arbitrary native command execution, calibration, output control, application selection, counting results, history, events or OPC UA PubSub. The information model is a PRECIZ vendor model, not the OPC UA Weighing or Device Integration companion model.

Three ways of obtaining a measurement serve different purposes:

Table 1

Interface

Use

Live variables and subscriptions

Display or continuously monitor individual values

ReadMeasurement

Obtain all eleven measurement fields from one current snapshot

CaptureStableWeight followed by GetCapturedMeasurement

Freeze a fresh valid stable measurement and retrieve it by request ID

2. Quick start

2.1 Enable the server

  1. Connect to Neutron's local configuration page or the Bluetooth configuration utility. Use HTTPS or authenticated Bluetooth for certificate/user management.

  2. Select the network connection interface and obtain its assigned IP address.

  3. Keep scale acquisition enabled in the Scale settings.

  4. Open the OPC UA tab. The firmware must report that OPC UA is available.

  5. For encrypted access, first create a user in Users & permissions.

  6. In Settings, enable the server, select the security mode, and retain port 4840 and minimum interval 100 ms for the initial connection.

  7. Click Save. Copy the connection address with Copy endpoint.

Example endpoint:

opc.tcp://192.168.50.73:4840

2.2 Connect using UAExpert

  1. Add the endpoint as a server in UAExpert.

  2. In encrypted mode select Basic256Sha256 / SignAndEncrypt and Username/Password authentication. In unprotected mode select None and Anonymous.

  3. For encrypted access, compare and trust Neutron's certificate. If the client certificate is not yet trusted by Neutron, follow section 4.2 and reconnect.

  4. Connect and browse Objects → CS-NEUTRON Scale. The object's NodeId is Scale; its displayed name is CS-NEUTRON Scale.

  5. Drag Gross, Net, Tare, Stable, Status, ErrorCode and Unit into Data Access View.

  6. Use the Data Access View context menu to set the subscription publishing interval and the monitored-item sampling interval, initially 100 ms.

Use a value only when its OPC UA StatusCode is Good. ErrorCode=1 means the native scale has no error. Status=1 or Status=3 describes a stable indication.

3. Connection and configuration

3.1 Endpoint and networking

The endpoint has the form opc.tcp://<assigned-device-IP>:<port>. Use the address of the selected Wi-Fi, Ethernet or LTE interface. The OPC UA tab displays the address and provides a copy button. A stable IP address simplifies integration.

The device does not need the PLC's IP address configured. Permit inbound TCP traffic to the selected port. The client must have a network route to Neutron; an LTE address behind carrier NAT is not automatically reachable from outside that network. Use the appropriate routed network, private APN or VPN.

3.2 Settings

Table 2

Setting

Key

Default

Values / effect

OPC UA available

OUB

Firmware dependent

Read-only: 0 absent, 1 available

Security support

OUS

Firmware dependent

Read-only: 0 absent, 1 available

OPC UA server

OUE

Disabled

0 disabled, 1 enabled

TCP port

OUP

4840

1024–65535; select an unused service port

Minimum update interval

OUI

100 ms

10–5000 ms; minimum sampling and publishing interval accepted by the server

Connection security

OUM

Unprotected

0 None/anonymous; 1 Basic256Sha256/SignAndEncrypt with username/password

Anonymous command access

OUC

Disabled

In unprotected mode only: 0 read-only; 1 all supported commands allowed

Saving OPC UA settings restarts the OPC UA service and disconnects its clients. User and trust changes also restart the service. Reconnect after these changes. Existing device IP, scale and clock settings are reused.

The minimum interval is a lower bound, not a fixed transmission period or a guarantee of end-to-end latency. Clients request their own intervals and must use the revised values returned by the server.

4. Security and permissions

4.1 Connection modes

Table 3

Mode

Policy / message security

Authentication

Command permission

Unprotected

None / None

Anonymous

Controlled by Anonymous command access

Encrypted

Basic256Sha256 / SignAndEncrypt

Username and password; trusted client application certificate

Controlled by the user's permission

In encrypted mode, anonymous sessions and certificate-based user login are not supported. The client application certificate identifies the client software; it does not replace username/password authentication. The web configuration PIN and HTTPS certificate are separate from OPC UA credentials and certificates.

Use unprotected mode on a trusted isolated network. It does not encrypt data or authenticate individual users.

4.2 First encrypted connection

  1. Open Neutron's OPC UA settings through HTTPS or authenticated Bluetooth.

  2. Add a user. Usernames contain 1–64 ASCII letters, digits, underscores or hyphens and are case-sensitive. Passwords contain 12–128 characters. Up to eight users are supported; there is no default OPC UA account.

  3. Select Read only or Read and execute commands.

  4. Enable encrypted OPC UA and save. The device clock must be synchronized and at least one user must exist. Secure startup waits for clock synchronization.

  5. At the first secure startup Neutron generates its private key and a self-signed RSA-2048 application certificate, valid for five years.

  6. In the client, compare Neutron's SHA-256 certificate fingerprint with the fingerprint displayed in the configuration interface, then trust it.

  7. Attempt the encrypted connection. Neutron rejects an unknown client application certificate and lists it under Certificates as rejected.

  8. Click Refresh certificates and users, compare the client's fingerprint, and click Approve for that certificate.

  9. Reconnect with the username and password.

The client must trust Neutron before it may proceed far enough to send its own certificate. Approval does not override expiry, signature, key-usage or application-URI validation.

4.3 Permissions

Table 4

Operation

Read only

Read and execute commands

Read variables / subscribe

Yes

Yes

ReadMeasurement

Yes

Yes

GetCapturedMeasurement

Yes

Yes

CaptureStableWeight

No

Yes

TareCurrent, SetTare, Zero, ClearTare

No

Yes

SetFilter, SetHRFilter

No

Yes

Write variables / administer users or certificates through OPC UA

No

No

Stored roles Reader and Operator correspond to these two permissions. There are no per-command permission levels. In encrypted mode the user permission applies; OUC is ignored. In unprotected mode OUC authorizes all supported commands or none.

Five failed logins impose a 30-second server-wide login block. This can temporarily affect other users as well. User passwords are stored as salted PBKDF2-HMAC-SHA256 hashes; the administration interface does not export passwords or private keys.

4.4 Device identity, CA certificates and renewal

Neutron's application URI is:

urn:preciz:cs-neutron:<MID>

The generated certificate includes this URI, the lowercase <MID>.local hostname and the device IP at generation time. Keep the address stable or issue a replacement certificate containing the addresses used by clients.

A CA certificate is not required for explicitly trusted self-signed application certificates. For company-managed PKI:

  1. Select Create and download CSR. The CSR uses the existing device key.

  2. Have the CA issue an OPC UA application certificate retaining the application URI in SAN and appropriate server/client extended key usages and digital-signature/key-encipherment usages.

  3. Import it as CA-signed device certificate. Its private key must match Neutron's existing key. Install the required CA chain in the client.

  4. To trust CA-issued clients, import the issuing root as Trusted client certificate or CA. Import intermediate CAs as Intermediate issuer CA. An intermediate issuer entry alone does not grant trust.

  5. Where revocation checking is used, import CA-signed CRLs as Certificate revocation list and update them before expiry. Import their issuer CAs first.

Supported imports are PEM or DER, up to 8192 bytes per file. Each trusted, rejected, issuer and CRL store holds up to 12 entries. Remove obsolete rejected entries when that store is full. Installed CRLs are checked for dates and issuer signature; expired CRLs reject affected new connections. Without installed CRLs, revocation checking is not performed. CRLs are not downloaded automatically; OCSP and GDS management are not provided.

Renew a certificate by creating a CSR and importing the renewed certificate. An expired device certificate prevents secure startup. Replace device identity removes the current key/certificate/CSR and generates a new identity at the next secure startup; clients must trust it again. Users and trusted clients are retained.

Users and certificate stores survive normal reboots and OTA updates. Erasing the device filesystem removes them. Before transferring device ownership, remove the previous users and trust entries explicitly.

5. Address space and data representation

5.1 Namespace and NodeIds

Vendor namespace URI:

urn:preciz:cs-neutron:weighing:1

Resolve this URI in Server/NamespaceArray at each connection. Do not hard-code namespace index 1 or 2. The version suffix :1 belongs to the stable namespace URI; the downloadable model version is 1.2.0.

Example forms for the same variable:

nsu=urn:preciz:cs-neutron:weighing:1;s=Scale.Gross
ns=2;s=Scale.Gross

The numeric form is valid only when the server currently assigns this URI to index 2. If a client does not accept nsu= syntax, resolve the URI and build the numeric-index NodeId. Vendor identifiers are case-sensitive strings, including the periods in Scale.Gross.

Table 5

Browse location

Object String NodeId

Objects / CS-NEUTRON Scale

Scale

Objects / Device

Device

Objects / Server

Standard namespace 0, numeric NodeId i=2253

Methods must be called with Scale as the parent ObjectId and the method's NodeId as MethodId.

5.2 Units and numeric precision

Gross, Net and Tare are exported as Double values normalized to the configured decimal places. HR is the high-resolution gross weight before display rounding, not net weight or raw ADC. Every weight uses the current Scale.Unit; OPC UA does not convert units. A Double transport type does not increase sensor accuracy.

Binary floating-point values do not represent every decimal exactly. Format display weights using Scale.Decimals and use Scale.Division as the weighing step. HR may appear in scientific notation: 9.31e-5 kg means 0.0000931 kg.

5.3 Time, snapshots and quality

Neutron copies the latest weighing values into the OPC UA snapshot approximately every min(OUI, 50) milliseconds, subject to acquisition availability. Reading or subscribing does not initiate another ADC conversion.

SourceTimestamp identifies the measurement snapshot time when the device clock is synchronized. It is absent before synchronization. ServerTimestamp is the server-provided timestamp for the DataValue; it need not equal SourceTimestamp. UTC is used for OPC UA timestamps.

Separate reads or subscription notifications may refer to different snapshots. Use ReadMeasurement or a captured result when fields must belong together. An unchanged monitored value need not produce a new notification every interval.

Table 6

DataValue StatusCode

Meaning / client action

Good

Value is usable; inspect Stable and native status as required

BadNoCommunication

No snapshot or more than two seconds without a new snapshot; discard live measurement

BadSensorFailure

Native scale error; inspect ErrorCode

BadOutOfRange

Underload or overload; discard measurement

Quality applies to weights, ADC and Stable. Status, ErrorCode and Unit remain readable during native scale errors, but become stale if snapshots stop. Command/capture diagnostics remain readable independently of live scale quality. Metadata is configuration information; its Good status does not establish that the live weighing result is valid.

6. Data reference

All entries below are read-only. NodeIds are vendor string identifiers unless identified as standard namespace 0. All scalar entries have ValueRank −1.

6.1 Live measurement and configuration

Table 7

String NodeId

Type

Unit

Description

Scale.Gross

Double

Scale.Unit

Rounded gross weight

Scale.Net

Double

Scale.Unit

Rounded net weight

Scale.Tare

Double

Scale.Unit

Applied tare

Scale.HR

Double

Scale.Unit

Unrounded high-resolution gross weight

Scale.ADC

Int32

ADC counts

Existing scale ADC value copied with the snapshot; no extra hardware read

Scale.Stable

Boolean

—

Scale stability flag

Scale.Status

UInt16

—

Indication status; table below

Scale.ErrorCode

UInt16

—

Native error; 1 means no error

Scale.Unit

String

—

Configured unit, such as kg or g

Scale.Decimals

UInt16

decimal places

Decimal-place count for displayed weight

Scale.Division

Double

Scale.Unit

Active weighing division

Scale.Capacity

Double

Scale.Unit

Active range capacity

Scale.Filter

UInt16

—

Active FT setting, 1–1023

Scale.HRFilter

Boolean

—

FC setting: false off, true on; controls ADC chopping

ADC is not a separate per-load-cell scan. No mV variable is exposed. Despite its name, HRFilter controls the existing FC/ADC chopping function, not a software filter applied exclusively to the OPC UA HR variable.

6.2 Native scale status

Table 8

Scale.Status

Meaning

0

Underload

1

Within zero range

2

Unstable

3

Stable

4

Overload

255

Uninitialized snapshot

Use Scale.Stable as the stability flag. Scale.Status and OPC UA StatusCode are separate concepts; a native status of 3 is not an OPC UA quality code.

6.3 Native error codes

Table 9

Scale.ErrorCode

Meaning

1

No error

99

Command timeout

98

Unknown command

97

Scale disabled

96

Calibration missing

95

Metrological data missing

94

ADC status register error

93

ADC reference error

92

ADC conversion mode error

91

ADC clock configuration error

90

ADC single-cycle configuration error

89

ADC rejection filter configuration error

88

ADC filter mismatch

87

ADC channel configuration error

86

ADC chopping mismatch

85

ADC bipolar mode error

84

ADC external reference configuration error

83

ADC gain mismatch

82

ADC averaging filter error

6.4 Measurement properties

Properties have the following vendor String NodeIds. Their BrowseNames are in namespace 0, for example 0:EngineeringUnits.

Table 10

String NodeId pattern

Type

Meaning

Scale.Gross.EngineeringUnits, Scale.Net.EngineeringUnits, Scale.Tare.EngineeringUnits, Scale.HR.EngineeringUnits

EUInformation

Unit metadata

Scale.Gross.EURange, Scale.Net.EURange, Scale.Tare.EURange, Scale.HR.EURange

Range

Low/High engineering range

Scale.Gross.ValuePrecision, Scale.Net.ValuePrecision, Scale.Tare.ValuePrecision

Double

Exported decimal-place count, equal to Decimals

EURange is [0, Capacity], except Net uses [-Capacity, Capacity]. Engineering range is metadata, not an instruction to clamp values. ValuePrecision is a decimal-place count, not the division or an accuracy specification. HR has no ValuePrecision property.

EngineeringUnits uses UN/CEFACT codes for kg (4933453), g (4674125), lb (4997714) and oz (5197402). Other unit symbols have UnitId −1 and an empty standards namespace. Refresh metadata after changes to units, range or scale configuration.

6.5 Command and capture diagnostics

Table 11

String NodeId

Type

Description

Scale.LastCommandId

UInt32

Latest accepted tare/zero/filter command ID

Scale.LastCommandState

UInt16

0 idle; 1 queued; 2 executing; 3 succeeded; 4 failed

Scale.LastCommandResult

String

Native response or rejection reason

Scale.LastCaptureId

UInt32

Latest accepted stable-capture request ID

Scale.LastCaptureState

UInt16

0 idle; 1 pending; 2 complete; 3 timeout

Command IDs and capture IDs are separate sequences. Both are shared by all clients, local to the running service, and reset when the service restarts.

6.6 Device identification

Table 12

String NodeId

Type

Description

Device.Manufacturer

String

PRECIZ

Device.Model

String

Device model

Device.SerialNumber

String

MID

Device.SoftwareRevision

String

Firmware version

Device.HardwareRevision

String

Hardware version

Device.DeviceName

String

Configured device name

Identity values are loaded when OPC UA starts. Restart the service after changing the device name to refresh DeviceName.

6.7 Standard server information

The following paths are relative to Objects / Server and use namespace 0.

Table 13

Browse path

Type / value

ServerArray

String[]; index 0 is the device application URI

NamespaceArray

String[]; index 0 is the OPC UA namespace, index 1 is the device application URI; resolve the vendor URI in this array

ServerStatus

ServerStatusDataType

ServerStatus/StartTime, CurrentTime

DateTime, declared UtcTime

ServerStatus/State

ServerState; 0 Running during normal operation

ServerStatus/SecondsTillShutdown

UInt32; 0 when no shutdown is scheduled

ServerStatus/ShutdownReason

LocalizedText

ServerStatus/BuildInfo

BuildInfo: ProductUri, ManufacturerName, ProductName, SoftwareVersion, BuildNumber, BuildDate

ServiceLevel

Byte; 255 during normal operation

Auditing

Boolean; false

VendorServerInfo

Vendor information object

ServerRedundancy/RedundancySupport

RedundancySupport; 0 None

ServerCapabilities/ServerProfileArray

String[]; implementation profile/facet URIs

ServerCapabilities/LocaleIdArray

LocaleId[]; en

ServerCapabilities/MinSupportedSampleRate

Duration in ms; active OUI minimum

ServerCapabilities/MaxBrowseContinuationPoints

UInt16; 5 per session

ServerCapabilities/SoftwareCertificates

SignedSoftwareCertificate[]; empty

ServerCapabilities/ModellingRules, AggregateFunctions

Folders

ServerCapabilities/OperationLimits

Per-request limits listed in section 9

Standard array variables have ValueRank 1 and ArrayDimensions [0]; zero denotes an unspecified maximum length. ServerProfileArray identifies the Micro Embedded Device 2017 implementation target and active transport/method/security facets. This profile identifier is not an OPC Foundation certification mark.

7. Methods and command execution

7.1 Method summary

Call each method on parent object Scale. Supply scalar arguments with the exact OPC UA types shown; do not substitute String, Int32 or Double for a UInt32 or Boolean argument.

Table 14

Method String NodeId

Input arguments

Output

Permission

Scale.ReadMeasurement

None

Eleven measurement fields, section 8.1

Read

Scale.CaptureStableWeight

TimeoutMs: UInt32

RequestId: UInt32

Execute

Scale.GetCapturedMeasurement

RequestId: UInt32

Eleven measurement fields, section 8.1

Read

Scale.TareCurrent

None

RequestId: UInt32

Execute

Scale.SetTare

Value: Double

RequestId: UInt32

Execute

Scale.Zero

None

RequestId: UInt32

Execute

Scale.ClearTare

None

RequestId: UInt32

Execute

Scale.SetFilter

Value: UInt16

RequestId: UInt32

Execute

Scale.SetHRFilter

Enabled: Boolean

RequestId: UInt32

Execute

7.2 TareCurrent

Tares the current stable gross weight using the native T operation. It sets tare to gross and net becomes zero; it does not change the gross zero point. The scale must accept the stable-tare operation within its command timeout.

Example with 1.11 kg on the scale: Gross remains 1.11 kg, Tare becomes 1.11 kg, and Net becomes 0.00 kg. A native success response resembles T S 1.11 kg.

7.3 SetTare

Sets a preset tare in Scale.Unit using the native TA operation. Value must be finite, nonnegative, no greater than 1,000,000,000 and no greater than capacity. The applied tare is rounded to the scale division. Read Scale.Tare after completion to obtain the applied value. Example input: Double 0.250 when Unit is kg.

7.4 Zero

Executes native Z, subject to stability and the configured zero range. On success the zero point is adjusted and existing applied/preset tare is cleared. The native success response is Z A. This is distinct from TareCurrent.

7.5 ClearTare

Executes native TAC, removing applied and preset tare. Gross is retained and Net returns to Gross. There are no input arguments.

7.6 SetFilter

Value is UInt16, 1–1023 inclusive. This sets FT for the active scale channel through the existing filter configuration handler. Zero and values above 1023 return BadOutOfRange. Example: UInt16 512.

7.7 SetHRFilter

Enabled is Boolean: true enables FC/ADC chopping, false disables it. A numeric value sent with a numeric OPC UA type is not a Boolean and is rejected.

FT and FC are activated and saved for the active channel through the native configuration handlers. Hardware verification failure produces an unsuccessful command result. Acquisition can pause while the setting is applied. Read Scale.Filter or Scale.HRFilter after completion to see the active setting.

7.8 Asynchronous command sequence

For TareCurrent, SetTare, Zero, ClearTare, SetFilter and SetHRFilter:

  1. Call the method and retain its returned RequestId.

  2. Read or subscribe to LastCommandId, LastCommandState and LastCommandResult.

  3. Associate the result only with a matching LastCommandId.

  4. State 3 means success; state 4 means failure. States 1 and 2 are pending.

  5. Read the affected process/configuration values after successful completion.

A Good Call result acknowledges acceptance, not completion. Only one of these commands can be queued/executing at a time; another receives BadResourceUnavailable. Existing scale stability, availability, busy and application interlocks still apply.

The command slot and last-result diagnostics are device-wide. Coordinate writers if two clients can issue commands: a later command may replace the last completed diagnostics before another client reads them. They are not a command history.

Request IDs are not durable operation IDs. After a connection loss, inspect the affected scale state before retrying a command whose outcome is unknown. A service restart clears diagnostics and cancels unfinished OPC UA-owned scale commands; it does not undo a completed tare, zero or setting change.

8. Consistent measurements and stable capture

8.1 ReadMeasurement output

ReadMeasurement() immediately returns the latest valid snapshot. It neither waits for stability nor requests a new ADC reading. GetCapturedMeasurement returns the same output signature for a frozen stable result.

Table 15

Position (zero-based)

Argument

OPC UA type

Meaning

0

MeasurementId

UInt64

Snapshot sequence number

1

Gross

Double

Gross weight

2

Net

Double

Net weight

3

Tare

Double

Applied tare

4

HR

Double

High-resolution gross weight

5

Stable

Boolean

Stability of this snapshot

6

Status

UInt16

Native scale status

7

ErrorCode

UInt16

Native scale error code

8

Unit

String

Unit for this result

9

Timestamp

DateTime

Snapshot UTC time, or zero if unsynchronized

10

TimeSynchronized

Boolean

Whether Timestamp is usable as calendar time

All fields belong to one snapshot. MeasurementId increments per OPC UA snapshot, not per physical ADC conversion, and resets with the service. Preserve UInt64 precision when storing it. ADC, metadata and filters are separate live nodes and are not included in this eleven-field method result.

If TimeSynchronized is false, do not interpret Timestamp as a calendar date. ReadMeasurement returns BadNoCommunication, BadSensorFailure or BadOutOfRange when the live snapshot is missing/stale, has a native error or is out of range.

8.2 CaptureStableWeight and GetCapturedMeasurement

  1. Call CaptureStableWeight(TimeoutMs) with UInt32 100–60000 ms. For example, 5000 allows up to five seconds for a valid stable measurement. Zero is invalid.

  2. Retain the returned UInt32 RequestId.

  3. Call GetCapturedMeasurement(RequestId) using that ID. While pending, it returns BadWaitingForInitialData. Repeat at a moderate interval such as 100 ms.

  4. On success, store the eleven-field result together with the capture RequestId.

Alternatively, subscribe to LastCaptureId and LastCaptureState, then retrieve the result when the matching request reaches state 2.

Table 16

LastCaptureState

Meaning

0

Idle

1

Pending

2

Complete; result available

3

Timeout

The captured snapshot must be published after the request starts and must be stable, fresh, free of native errors and within range. Invalid snapshots are skipped until a suitable one arrives or the timeout expires. If the scale is already stable, the next valid snapshot can complete the capture immediately; no unstable-to-stable transition or additional hold period is required.

The operation does not tare or zero the scale and does not block other clients. Only one capture can be pending. There is one frozen result for the whole device, shared by all clients. It remains unchanged even if the live weight changes or becomes unavailable. Starting a new capture supersedes the previous request/result. There is no capture history.

Table 17

GetCapturedMeasurement result

Meaning

Good

Frozen result returned

BadWaitingForInitialData

Matching capture still pending

BadTimeout

Matching capture expired without a valid stable measurement

BadNotFound

ID is zero, unknown, superseded or no longer available after restart

BadNoData

No completed result for the matching capture state

Use the capture RequestId, not the result's MeasurementId, as input to GetCapturedMeasurement. The capture may finish after its initiating client disconnects. It can be retrieved after reconnecting with the same ID if the OPC UA service has remained running. A service restart clears pending captures, stored results and IDs; coordinate capture requests between clients.

9. Subscriptions, timing and capacity limits

9.1 Timing

Table 18

Parameter

Meaning

OUI

Configured lower bound for sampling and publishing

Sampling interval

How often a monitored item is sampled

Publishing interval

How often the subscription can publish queued notifications

Queue size

Number of notifications retained per monitored item

Keepalive

Indicates an active subscription when there are no notifications

Start with 100–250 ms and queue size 1 for a live display. For the fastest available update, set OUI to 10 ms, reconnect after saving, and request 10 ms sampling/publishing. Use the server's revised intervals in client logic.

Sampling faster than the physical acquisition rate does not create new measurements. Network latency, encryption, client load and publishing settings affect observed response time. UAExpert's Server Status / Response Time is not the subscription's sampling or publishing interval.

9.2 Capacity and per-request limits

Table 19

Resource

Limit

SecureChannels

4 total, including reconnect overlap

Sessions

2 simultaneous

Session timeout

Maximum negotiated timeout 30 seconds

Subscriptions

4 total; 2 per session

Monitored items

64 total; 32 per subscription

Monitored-item queue

1–16 values per item

Pending Publish requests

4 per session

Retransmission queue

16 messages per subscription

Browse continuation points

5 per session

Minimum sampling/publishing

OUI, 10–5000 ms; default 100 ms

Read / Write / Browse operations

32 per request

RegisterNodes / TranslateBrowsePaths operations

32 per request

Method Call operations

8 per request

Monitored-item operations

32 per request

These are server-wide totals unless a per-session/per-subscription scope is stated. If the Publish request queue is full, the oldest pending request receives BadTooManyPublishRequests so a new request can be queued. Acknowledgements and Republish operate on the bounded retransmission queue. The Write operation limit does not make read-only variables writable.

Close sessions cleanly. A disconnected client may leave its previous session occupying a slot until it expires. Reuse/reactivate an existing session where supported; otherwise wait for expiry. A new server instance cannot reactivate a session from before service restart: create a session, resolve namespaces and recreate subscriptions. Non-consuming TCP clients can be disconnected after a one-second send deadline.

10. Integration examples

10.1 UAExpert: stable capture

  1. Browse CS-NEUTRON Scale, right-click CaptureStableWeight, and select Call.

  2. Enter TimeoutMs 5000 and click Call. Record the returned RequestId.

  3. Open GetCapturedMeasurement and enter the same RequestId.

  4. Click Call. If pending, call GetCapturedMeasurement again with the same ID.

  5. Read Gross, Net, Tare, HR, Stable, Status, ErrorCode, Unit and Timestamp from the returned result. Leave the existing capture request running while waiting; do not repeatedly start new captures.

10.2 Python: secure connection, coherent read and optional capture

Install the client package in a Python virtual environment:

python -m pip install asyncua

Prepare an OPC UA client application certificate and private key. Its SAN application URI must match CLIENT_URI below. Approve its certificate on Neutron and download Neutron's certificate as neutron.der. Replace the endpoint, username and client URI with your values. The private key file in this example is accessible to the Python client; it is not Neutron's private key.

import asyncio
import getpass

from asyncua import Client, ua
from asyncua.crypto.security_policies import SecurityPolicyBasic256Sha256
from asyncua.ua.uaerrors import UaStatusCodeError

URL = "opc.tcp://192.168.50.73:4840"
NS_URI = "urn:preciz:cs-neutron:weighing:1"
CLIENT_URI = "urn:example:neutron-client"
FIELDS = ("MeasurementId", "Gross", "Net", "Tare", "HR", "Stable",
          "Status", "ErrorCode", "Unit", "Timestamp", "TimeSynchronized")
CAPTURE = False  # Set True when logged in with command permission.


async def main():
    client = Client(URL, timeout=10)
    client.application_uri = CLIENT_URI
    await client.set_security(
        SecurityPolicyBasic256Sha256,
        certificate="client.der",
        private_key="client-key.pem",
        server_certificate="neutron.der",
        mode=ua.MessageSecurityMode.SignAndEncrypt,
    )
    client.set_user(input("Username: "))
    client.set_password(getpass.getpass("Password: "))

    async with client:
        ns = await client.get_namespace_index(NS_URI)
        scale = client.get_node(ua.NodeId("Scale", ns))

        def method(name):
            return ua.NodeId("Scale." + name, ns)

        values = await scale.call_method(method("ReadMeasurement"))
        result = dict(zip(FIELDS, values))
        print("Current snapshot:", result)

        if CAPTURE:
            request_id = await scale.call_method(
                method("CaptureStableWeight"),
                ua.Variant(5000, ua.VariantType.UInt32),
            )
            deadline = asyncio.get_running_loop().time() + 7
            while True:
                try:
                    values = await scale.call_method(
                        method("GetCapturedMeasurement"),
                        ua.Variant(request_id, ua.VariantType.UInt32),
                    )
                    print("Capture", request_id, dict(zip(FIELDS, values)))
                    break
                except UaStatusCodeError as exc:
                    if exc.code != ua.StatusCodes.BadWaitingForInitialData:
                        raise
                    if asyncio.get_running_loop().time() >= deadline:
                        raise TimeoutError("Client capture wait expired") from exc
                    await asyncio.sleep(0.1)


asyncio.run(main())

ReadMeasurement requires valid live data. Exceptions such as BadSensorFailure or BadOutOfRange must be handled by the calling application. BadTimeout from GetCapturedMeasurement means the server's capture timeout expired; it is not a reason to reuse an old stored measurement as a new successful capture.

10.3 Python: subscribe to live weight

The following code runs inside an established async with client connection. The handler checks quality before using the value.

class WeightHandler:
    def datachange_notification(self, node, value, data):
        status = data.monitored_item.Value.StatusCode
        if status.is_good():
            print(node.nodeid.to_string(), value)
        else:
            print("Invalid measurement:", status)


ns = await client.get_namespace_index(NS_URI)
gross = client.get_node(ua.NodeId("Scale.Gross", ns))
subscription = await client.create_subscription(100, WeightHandler())
try:
    await subscription.subscribe_data_change(gross, queuesize=1)
    await asyncio.sleep(30)
finally:
    await subscription.delete()

The requested publishing interval is 100 ms. Configure monitored-item sampling through the client library as needed and honor revised server values.

10.4 PLC integration sequence

Use the OPC UA client blocks supplied by the PLC manufacturer. Resolve String NodeIds using the vendor namespace URI. The following is a vendor-neutral sequence, not a specific PLC programming-language implementation:

CONNECT -> TRUST / AUTHENTICATE -> RESOLVE NAMESPACE URI
        -> RESOLVE Scale object and required variable/method NodeIds
        -> CREATE SUBSCRIPTION -> MONITOR LIVE DATA

On a stable-result request:
  Call Scale.CaptureStableWeight(TimeoutMs := UInt32(5000))
  Save returned RequestId
  Call Scale.GetCapturedMeasurement(RequestId)
    BadWaitingForInitialData -> wait 100 ms and repeat retrieval
    Good                    -> store the eleven fields as one record
    BadTimeout              -> report no stable result
    Other failure           -> handle the error; do not use old data

On tare request:
  Call Scale.TareCurrent()
  Save returned command RequestId
  Wait for matching LastCommandId and LastCommandState 3 or 4
  On success read Gross / Net / Tare; on failure read LastCommandResult

Map UInt64 MeasurementId to an appropriate PLC integer type. Do not send a numeric Boolean substitute to SetHRFilter. Serialize commands and stable-capture ownership in the PLC/application when multiple clients have command permission.

11. Troubleshooting, downloads and compatibility

11.1 Connection and method errors

Table 20

Symptom / status

Meaning and action

BadCommunicationError / connection refused

Confirm OPC UA is enabled, endpoint IP/port, selected network route and firewall. The startup log must contain OPC UA listening on port ...

BadCertificateUntrusted

Trust Neutron in the client and approve the client certificate in Neutron, or install the appropriate CA chain

Certificate time/URI errors

Synchronize clocks and use a certificate with valid dates and the client's configured application URI

BadIdentityTokenRejected / BadUserAccessDenied

Use the correct username/password and required command permission; wait out the 30-second block after repeated login failures

BadTooManySessions / session limit reached

Two slots are occupied; disconnect another client or wait for an abandoned session to expire

BadNodeIdUnknown

Resolve the vendor namespace URI again, check the case-sensitive String NodeId and firmware/model compatibility

BadTypeMismatch

Use the exact scalar argument type from section 7.1

BadOutOfRange on CaptureStableWeight

Timeout must be UInt32 100–60000; zero is invalid

BadOutOfRange on SetFilter / SetTare

Use FT 1–1023 or a finite nonnegative tare within capacity and 1e9

BadResourceUnavailable

Command slot or capture slot is busy; wait for its current operation

Command Call is Good but operation fails

Inspect matching LastCommandState and LastCommandResult; Good only acknowledged queueing

BadNotWritable on variable writes

Process variables are read-only; use the supported method

Capture BadWaitingForInitialData

Keep retrieving the same capture ID; the server is waiting for a valid stable sample

Capture BadTimeout

No qualifying stable sample arrived before the deadline

Capture BadNotFound

Use the returned capture RequestId; a newer capture or service restart invalidated the old ID

Missing ServerCapabilities after firmware change

Refresh the address space or reconnect with a fresh client project to discard cached browse results

Blank/stale measurements

Keep scale acquisition enabled, inspect ErrorCode and native status, and check DataValue quality

11.2 Downloads and related manuals

NodeSet2 describes the vendor address space, method arguments, references and types for offline model tools. Its namespace indexes are local to that XML file; resolve the namespace URI on the live device. The XML contains model definitions, not current measurements or a backup of users/certificates/settings. Runtime intervals and executable permissions follow the active device configuration.

11.3 Version compatibility

Table 21

Information model

Interface additions

1.0

Base weighing values and tare/zero methods

1.1.0

Measurement metadata, identification, coherent measurement and stable capture

1.2.0

ADC, FT/FC values and SetFilter/SetHRFilter

The namespace URI remains urn:preciz:cs-neutron:weighing:1. Existing method signatures are retained; ReadMeasurement/GetCapturedMeasurement return eleven fields. Select firmware containing OPC UA and the functions required by the integration. A firmware build without OPC UA cannot expose an endpoint.

Frequently asked questions

Does Neutron support encrypted OPC UA?

Yes. Select Basic256Sha256 / SignAndEncrypt, use a username and password, and establish mutual trust in application certificates. Unprotected None/Anonymous mode is also available.

How do I obtain one consistent stable measurement?

Call CaptureStableWeight with a UInt32 timeout of 100–60000 ms, retain its RequestId and retrieve the eleven-field result with GetCapturedMeasurement using that same ID. While pending, retrieve again instead of starting another capture.

Does a Good method call mean the command has completed?

For tare, zero and filter commands, Good confirms acceptance. Match LastCommandId to the returned RequestId and wait for LastCommandState 3 (success) or 4 (failure).

Which namespace URI and model version should I use?

Resolve urn:preciz:cs-neutron:weighing:1 in NamespaceArray on every connection. The downloadable information model is version 1.2.0; a numeric namespace index such as 2 is only an example.